TY - GEN
T1 - Techno-Economic Analysis of Geologically Connected Seawater Air Conditioning (GeoSWAC) Concept for District Cooling at the University of Puerto Rico at Rio Piedras
AU - Oh, Hyunjun
AU - Winick, Jeffrey
AU - Davalos Elizondo, Estefanny
AU - Bonnema, Eric
AU - Akinwonmi, Remi
AU - Acero-Allard, Diana
PY - 2025
Y1 - 2025
N2 - At the University of Puerto Rico at Rio Piedras, a central chilled water plant supplies cooling to several campus buildings, contributing significantly to electricity demand during daytime peak hours, particularly in the summer months. These operational challenges are exacerbated by Puerto Rico's tropical rainforest climate and a power grid vulnerable to frequent disruptions caused by hurricanes and tropical storms. This study presents a techno-economic analysis of the existing chilled water plant serving four representative campus buildings and introduces a conceptual alternative: the Geologically connected Seawater Air Conditioning (GeoSWAC) system. GeoSWAC leverages stable low temperatures of deep ocean water (~1 km depth), hydraulically connected to an inland well, to deliver cooling without the use of vapor-compression refrigeration. Using modeled annual cooling loads and chiller performance data, capital costs, energy consumption, and levelized cost of cooling (LCOC) were evaluated for both systems. While GeoSWAC showed higher capital costs than the chiller-based scenario, operational costs were significantly lower at $26k-$53k annually, resulting in a lower LCOC between $2.3/MWh and $8.2/MWh compared to $30.2/MWh-$33.6/MWh for the chiller scenario. These results suggest that the GeoSWAC system offers a promising, low-energy, and climate-resilient alternative for large-scale cooling in tropical coastal environments, with significant potential to reduce peak electricity demand and improve long-term system reliability.
AB - At the University of Puerto Rico at Rio Piedras, a central chilled water plant supplies cooling to several campus buildings, contributing significantly to electricity demand during daytime peak hours, particularly in the summer months. These operational challenges are exacerbated by Puerto Rico's tropical rainforest climate and a power grid vulnerable to frequent disruptions caused by hurricanes and tropical storms. This study presents a techno-economic analysis of the existing chilled water plant serving four representative campus buildings and introduces a conceptual alternative: the Geologically connected Seawater Air Conditioning (GeoSWAC) system. GeoSWAC leverages stable low temperatures of deep ocean water (~1 km depth), hydraulically connected to an inland well, to deliver cooling without the use of vapor-compression refrigeration. Using modeled annual cooling loads and chiller performance data, capital costs, energy consumption, and levelized cost of cooling (LCOC) were evaluated for both systems. While GeoSWAC showed higher capital costs than the chiller-based scenario, operational costs were significantly lower at $26k-$53k annually, resulting in a lower LCOC between $2.3/MWh and $8.2/MWh compared to $30.2/MWh-$33.6/MWh for the chiller scenario. These results suggest that the GeoSWAC system offers a promising, low-energy, and climate-resilient alternative for large-scale cooling in tropical coastal environments, with significant potential to reduce peak electricity demand and improve long-term system reliability.
KW - district cooling
KW - district energy
KW - GeoSWAC
KW - Puerto Rico
KW - reservoir thermal energy storage
KW - techno-economic analysis
U2 - 10.2172/3015047
DO - 10.2172/3015047
M3 - Presentation
T3 - Presented at the 2025 Geothermal Rising Conference, 26-29 October 2025, Reno, Nevada
ER -