Skip to main navigation Skip to search Skip to main content

Meta-Analysis of Field Demonstrations Using Phase Change Material in Commercial Building Ceilings

  • Jason LaFleur
  • , Chuck Booten
  • , Andy Lick
  • , Alex Cicelsky
  • , Sajith Wijesuriya
  • , Habib Arjmand Mazidi
  • , Mario Medina
  • , Ravi Kishore
  • , Barry Dicker
  • GTI Energy
  • Slipstream Group
  • Milwaukee School of Engineering
  • Texas A&M University
  • Decent Energy, Inc

Research output: Contribution to conference › Paper

Abstract

Phase change material (PCM) technology leverages materials that absorb and release latent heat during phase transitions to help regulate indoor temperatures. Several commercialized products incorporate PCMs into standard commercial ceiling tiles, or into mats installed above the finish ceiling, adding passive thermal mass. These products have specific freeze/melt temperatures to manage peak cooling and heating loads, improve mechanical system runtimes, enhance thermal stability, and increase occupant comfort. This paper describes the results of multiple studies that evaluate how installing PCM mats above commercial ceiling tiles impacts the operation of heating, ventilation, and air-conditioning (HVAC) systems in six buildings across ASHRAE climate zones 4A, 5A, and 6A, using products from multiple manufacturers. Field locations were evaluated in both pre- and post-retrofit scenarios and the post retrofit evaluation is presented in this paper, comparing factors such as impact on facility energy usage, HVAC runtime, temperatures in the space, and occupant comfort across heating and cooling seasons. Results were mixed: Some applications show minor reductions in HVAC cycling frequency, but others show extended HVAC runtimes during peak demand periods. However, overall energy reduction in commercial buildings was ambiguous unless coupled with strategies to actively cycle the PCM-enhanced ceilings, such as using the building control systems to force freeze and thaw cycles. Without active control, there were minimal measured energy savings and therefore limited cost-effectiveness. PCM-enhanced ceilings may provide other benefits not accounted for in a payback analysis, such as improving occupant comfort or providing thermal stability. The findings suggest PCM in commercial buildings provides limited benefits as a stand-alone passive control mechanism, with greater value possible when coupled with a means to actively control the freeeze and thaw cycles.
Original languageAmerican English
Number of pages9
DOIs
StatePublished - 2025
EventBuildings XVI - Clearwater Beach, FL
Duration: 8 Dec 2025 → 11 Dec 2025

Conference

ConferenceBuildings XVI
CityClearwater Beach, FL
Period8/12/25 → 11/12/25

NLR Publication Number

  • NLR/CP-5500-94070

Keywords

  • field test
  • model calibration
  • PCM
  • phase change materials
  • thermal energy storage
  • thermal storage

Fingerprint

Dive into the research topics of 'Meta-Analysis of Field Demonstrations Using Phase Change Material in Commercial Building Ceilings'. Together they form a unique fingerprint.

Cite this