Skip to main navigation Skip to search Skip to main content

Evaluating Protection System Performance for a Real-World Weak Grid Area With High Inverter-Based Resources: Preprint

  • Florida Power & Light Company

Research output: Contribution to conference › Paper

Abstract

This paper evaluates an existing protection scheme implemented in a real-world weak grid area with a high penetration of inverter-based resources (IBRs). The study aims to assess the reliability and adequacy of protection schemes originally designed for traditional synchronous machine systems and determine whether they can continue to operate reliably in systems with high levels of IBRs. Hardware relays are tested using a controller-hardware-in-the-loop setup. PSCAD electromagnetic transient simulation with an IBR original equipment manufacturer black-box model is used to perform fault studies and generate COMTRADE data, which are replayed by a real-time digital simulator (RTDS) to feed input to the hardware relays. Three scenarios are analyzed: normal operation, an N-1 contingency, and an IBR-only scenario. The evaluation results reveal the following: 1) the protection scheme remains reliable under normal conditions and N-1 contingencies and 2) in IBR-only scenarios, differential protection (87L) continues to operate reliably, whereas local protection elements, such as distance and directional elements, fail because of the lack of regulated negative sequence current contributed by IBRs. These findings provide utilities with valuable insights for improving their protection systems in high-IBRs.
Original languageAmerican English
Number of pages8
StatePublished - 2026
EventIEEE PESGM 2026 - Montral, Canada
Duration: 19 Jul 2026 → 23 Jul 2026

Conference

ConferenceIEEE PESGM 2026
CityMontral, Canada
Period19/07/26 → 23/07/26

NLR Publication Number

  • NLR/CP-5D00-98156

Keywords

  • enhanced protection
  • IEEE 2800-2022
  • negative sequence current
  • transmission line protection

Fingerprint

Dive into the research topics of 'Evaluating Protection System Performance for a Real-World Weak Grid Area With High Inverter-Based Resources: Preprint'. Together they form a unique fingerprint.

Cite this