Skip to main navigation Skip to search Skip to main content

Evaluating Protection System Performance for a Real-World Weak Grid Area With High Inverter-Based Resources

  • Florida Power & Light Company

Research output: NLR › Poster

Abstract

This paper evaluates an existing protection scheme implemented in a real-world weak grid area with a high penetration of inverter-based resources (IBRs). The study aims to assess the reliability and adequacy of protection schemes originally designed for traditional synchronous machine systems and determine whether they can continue to operate reliably in systems with high levels of IBRs. Hardware relays are tested using a controller-hardware-in-the-loop setup. PSCAD electromagnetic transient simulation with an IBR original equipment manufacturer black-box model is used to perform fault studies and generate COMTRADE data, which are replayed by a realtime digital simulator (RTDS) to feed input to the hardware relays. Three scenarios are analyzed: normal operation, an N-1 contingency, and an IBR-only scenario. The evaluation results reveal the following: 1) the protection scheme remains reliable under normal conditions and N-1 contingencies and 2) in IBRonly scenarios, differential protection (87L) continues to operate reliably, whereas local protection elements, such as distance and directional elements, fail because of the lack of regulated negative sequence current contributed by IBRs. These findings provide utilities with valuable insights for improving their protection systems in high-IBRs.
Original languageAmerican English
PublisherNational Laboratory of the Rockies (NLR)
Number of pages1
DOIs
StatePublished - 2026

Publication series

NamePresented at the 2026 IEEE Power and Energy Society General Meeting, 19-23 July 2026, Montreal, Canada

NLR Publication Number

  • NLR/PO-5D00-101337

Keywords

  • direction element
  • distance elment
  • IEEE 2800-2022
  • power system protection

Fingerprint

Dive into the research topics of 'Evaluating Protection System Performance for a Real-World Weak Grid Area With High Inverter-Based Resources'. Together they form a unique fingerprint.

Cite this