Analysis of Line Distance Elements for Various Ibr Controllers and System Conditions: Article No. 112370

  • Paulo Pinheiro
  • , Bruno Franca
  • , Yona Lopes
  • , Soham Chakraborty
  • , Romulo Bainy
  • , Hangtian Lei
  • , Brian Johnson
  • , Scott Manson
  • , Jing Wang
  • , Rasel Mahmud
  • , Andy Hoke
  • , Cameron Kruse
  • Universidade Federal Fluminense
  • University of Idaho
  • Schweitzer Engineering Laboratories, Inc.
  • Kauai Island Utility Cooperative

Research output: Contribution to journal › Article › peer-review

4 Scopus Citations

Abstract

The large-scale penetration of inverter-based resources in power systems has challenged protection engineers because of the different fault behaviors these sources provide compared to conventional generation systems. The main challenges include a low level of fault current magnitude, unpredictable angles of sequence currents, and lack of inertia that can lead to maloperation of conventional phasor-based protection elements. This paper presents a sensitivity analysis of transmission line distance protection elements during phase-to-ground and phase-to-phase faults for different inverter controllers and power system conditions. It also summarizes which line protection elements remain secure near IBR terminations and identifies the ones affected by the inverter-based response. The paper concludes by highlighting that regulating negative-sequence current injection during the fault aids correct protection decisions, but does not address the entire challenge. Finally, alternative protection elements to those affected by the inverter fault response are discussed.
Original languageAmerican English
Number of pages7
JournalElectric Power Systems Research
Volume252
DOIs
StatePublished - 2026

NLR Publication Number

  • NLR/JA-5D00-99057

Keywords

  • distance protection
  • grid following inverters
  • inverter-based resources
  • transmission lines

Fingerprint